Sichuan University, Chengdu, Sichuan, 610000, China
Vol. 3, Issue 1, Pages: 20-23(2026)
Doi:https://doi.org/10.62639/sspjinss03.20260301
ISSN:3006-0729
EISSN:3006-4287
188
Downloads:0
Focusing on the high-energy electrons generated by air ionization in ultra-high voltage AC and DC transmission lines, the coupling of space charge and aging in typical insulation systems such as cross-linked polyethylene ( XLPE ) and oil-paper is analyzed. The mutual constraints of space charge capture-release kinetics, trap energy level structure and electrical tree initiation-expansion process under strong electric field / heating conditions are focused, and the remodeling of electric field distortion and degradation path is discussed accordingly. Under DC condition, the charge injection and migration are more sensitive to aging, and the space charge accumulation caused by the increase of trap depth and density enlarges the local field strength more significantly, thus compressing the insulation redundancy and breakdown threshold.
KeywordHigh voltage cable;Insulation aging;Space charge;Electrical treeing;Electric field characteristics